A Grid-Forming Converter with MVDC Supply and Integrated Step-Down Transformer: Modeling, Control Perspectives, and Control Hardware-in-the-Loop (C-HIL) Verification

Saeed Golestan Orcid Logo, Manuel Barrios Orcid Logo, Hessam Golmohamadi, Florin Iov Orcid Logo, Birgitte Bak-Jensen Orcid Logo, Mohammad Monfared Orcid Logo

Electronics, Volume: 13, Issue: 16, Start page: 3143

Swansea University Author: Mohammad Monfared Orcid Logo

  • 67356.VoR.pdf

    PDF | Version of Record

    © 2024 by the authors. This is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license.

    Download (5.49MB)

Abstract

A grid-forming voltage source converter with an integrated step-down transformer could be a promising solution for supplying low-voltage alternating current loads from a medium-voltage direct current supply. However, it may require a control system that gathers feedback signals from both the primary...

Full description

Published in: Electronics
ISSN: 2079-9292
Published: MDPI AG 2023
Online Access: Check full text

URI: https://cronfa.swan.ac.uk/Record/cronfa67356
Tags: Add Tag
No Tags, Be the first to tag this record!
Abstract: A grid-forming voltage source converter with an integrated step-down transformer could be a promising solution for supplying low-voltage alternating current loads from a medium-voltage direct current supply. However, it may require a control system that gathers feedback signals from both the primary and secondary sides of the transformer, which in turn complicates the derivation of a standard form linear model. The absence of such a model complicates control tuning, as well as the assessment of dynamics and stability of the converter system. The objective of this paper is to address this gap in knowledge. For the case study, a conventional H-bridge converter with a step-down transformer and an -frame dual-loop grid-forming controller is considered. Initially, comprehensive guidelines on deriving a standard form linear model for this converter system are presented. Then, the impact of controlling the VSC in a frame and the changes in the transformer vector group on the small-signal model of the VSC are analyzed. The aspects of control tuning are also discussed in detail, and the model’s accuracy and efficacy are validated both theoretically and through control hardware-in-the-loop (C-HIL) tests using a Typhoon HIL setup.
Keywords: control hardware-in-the-loop (C-HIL); control tuning; grid-forming control; low-voltage alternating current (LVAC); medium-voltage direct current (MVDC); small-signal modeling; transformer; voltage source converter (VSC); voltage control